The error log, Figure 26 module-specific diagnostic counters – Rockwell Automation AutoMax ControlNet Communication Interface Module User Manual

Page 66

background image

Page 66 AutoMax ControlNet Module

Publication number DSMBCN-UM001B-EN-P February 2003

Name

Location Description

ReplySentOk

9385

High Level Replies Sent OK

ReplyRecdOk

9386

High Level Replies Received OK

DuplMsgsRecd

9387

Duplicate Messages Received (and ignored)

AckTout

9388

UCMM Acknowledge Timeouts

TxFail

9389

High Level Transmit Failures, the MBCN tried
3 times to send a message, there was no
acknowledge, no reply

UndelivReply

9390

High Level Reply could not be delivered

ConnTimeout 9391

Connection

TimeOuts

MsgsIgnored

9392

Messages Ignored, caused by other nodes
sending diagnostic messages on the network

MsgsIgnType

9393

Type of Message Ignored

FreeUnsBufs

9394

Free Unscheduled Buffers

FreeHeapBlks

9395

Free Internal Heap Blocks

EventOveruns 9396

Event

Overruns

ConnRetries

9397

Connected Message retries

ConnRefSts

9398-9399 The status of the last refused connection. The

upper byte of 9399 contains the general status.
The lower byte of 9399 contains the length of
the extended status, either 0 (no extended
status) or 2. Register 9398 contains the
extended status, if present.

NapRxBad

9400

NAP frames received with a bad CRC

NapRxAbt

9401

NAP receive abort frames

Figure 26 Module-Specific Diagnostic Counters

The Error Log

Registers 9336-9339 contain the error log. This is a log of the source
addresss for the last eight messages with CRC errors or transmit abort
errors. Each register contains two error log entries, one byte each.

NOTE: Since these errors occur when the MBCN receives bad packets,
the contents of the log may not be valid, but it may be useful in
identifying problem nodes.

The error log is a ring buffer.