The error log, Figure 26 module-specific diagnostic counters – Rockwell Automation AutoMax ControlNet Communication Interface Module User Manual
Page 66
![background image](/manuals/581117/66/background.png)
Page 66 AutoMax ControlNet Module
Publication number DSMBCN-UM001B-EN-P February 2003
Name
Location Description
ReplySentOk
9385
High Level Replies Sent OK
ReplyRecdOk
9386
High Level Replies Received OK
DuplMsgsRecd
9387
Duplicate Messages Received (and ignored)
AckTout
9388
UCMM Acknowledge Timeouts
TxFail
9389
High Level Transmit Failures, the MBCN tried
3 times to send a message, there was no
acknowledge, no reply
UndelivReply
9390
High Level Reply could not be delivered
ConnTimeout 9391
Connection
TimeOuts
MsgsIgnored
9392
Messages Ignored, caused by other nodes
sending diagnostic messages on the network
MsgsIgnType
9393
Type of Message Ignored
FreeUnsBufs
9394
Free Unscheduled Buffers
FreeHeapBlks
9395
Free Internal Heap Blocks
EventOveruns 9396
Event
Overruns
ConnRetries
9397
Connected Message retries
ConnRefSts
9398-9399 The status of the last refused connection. The
upper byte of 9399 contains the general status.
The lower byte of 9399 contains the length of
the extended status, either 0 (no extended
status) or 2. Register 9398 contains the
extended status, if present.
NapRxBad
9400
NAP frames received with a bad CRC
NapRxAbt
9401
NAP receive abort frames
Figure 26 Module-Specific Diagnostic Counters
The Error Log
Registers 9336-9339 contain the error log. This is a log of the source
addresss for the last eight messages with CRC errors or transmit abort
errors. Each register contains two error log entries, one byte each.
NOTE: Since these errors occur when the MBCN receives bad packets,
the contents of the log may not be valid, but it may be useful in
identifying problem nodes.
The error log is a ring buffer.