Unscheduled Messaging

The MBCN supports unscheduled messaging to other nodes on the
ControlNet network. It emulates the interface of the M/N 57C442 Data
Highway Plus module. It uses PCCC commands to communicate with
other nodes on the network.

This section describes how the messaging interface is organized in the
MBCN and provides examples of how the MBCN is accessed by the
application software. For more detailed information on programming,
refer to the AutoMax Programming Language manuals.

The MBCN supports sending messages on the local network only, not
through bridge modules.

Register Organization

The following table shows the memory organization. The following
sections describe the different register areas in more detail.

Registers

Description

4 – 63

Status and control registers

64 – 1063

Binary file B3

1088 – 2087

Binary file B4

2088 – 3087

Binary file B5

4384 – 5383

Integer file N7

5384 – 6383

Integer file N8

6384 – 7383

Integer file N9

Figure 9 Summary of Unscheduled Message Registers

WARNING

REGISTERS AND BITS THAT ARE DESCRIBED AS "READ
ONLY" OR FOR "SYSTEM USE" ONLY MUST NOT BE WRITTEN
TO BY THE USER. WRITING TO THESE REGISTERS AND BITS
MAY RESULT IN IMPROPER SYSTEM OPERATION. FAILURE
TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY
INJURY.