Summary of registers for monitoring operation, Figure 6 scanner state table – Rockwell Automation AutoMax ControlNet Communication Interface Module User Manual

Page 39

background image

AutoMax ControlNet Module Page

39

Publication number DSMBCN-UM001B-EN-P February 2003

If bit 3 is set, one or more originator instances does not have a schedule.
Run RSNetWorx and schedule the network by enabling edits and doing a
save.

Scanner State

Register 15754 shows the current scanner state.

Value

Scanner State

0 Idle

1

Active, in program mode

2

Active, in run mode

Figure 6 Scanner State Table

This register is read-only. The state is Idle only when you are
downloading a configuration.

Adapter State

Register 15755 shows the current state of scheduled produced data
connections.

Value

State

0 Idle

1 Enabled

Figure 7 – Adapter (Scheduled Produced Data) State Table

This register is read-only.

Summary of Registers for Monitoring Operation

Refer to the preceding sections for detailed information on each of these
registers.

AutoMax

Registers

Name

Description

15362 -

15615

Connection
status

Status of each connection

15745 Status

Overall

status

15748

NumInstances

Number of instances currently
configured

15751

NumOrigInsts

Number of originator instances

15754

ScanState

Current scanner state