Compile the code -17, Compile the code – Rockwell Automation 1753-PCS-PAR Using RSLogix Guard PLUS! with GuardPLC Controllers User Manual
Page 57

Publication 1753-PM001A-EN-P - November 2005
Create a GuardPLC Project 3-17
2. Click OK
Compile the Code
1. Close the Type Instance Program.
2. Right-click Resource and choose Code Generation.
3. The results of the code generation are shown on the Error State
Viewer.
If the Error State Viewer is not visible, click the red triangle
to make it visible.
If the compile was successful, ‘Error Free code generated’ appears in
the Error-State Viewer.
TIP
The FB editor menu bar displays the number of
edits since the last save. Following a save, it
displays ‘(unchanged)’.
TIP
If you are using a GuardPLC 1800 controller, you will
see a warning in the Error State Viewer. Go to the
Hardware Management window to view the
warning, which reads ‘USED’ has an initial value, but
no source.’ Disregard this warning, because the
‘USED’ signal has an initial value of 1, but no source
drives its value.