Firmware and software version compatibility – Rockwell Automation 1753-PCS-PAR Using RSLogix Guard PLUS! with GuardPLC Controllers User Manual
Page 102
Publication 1753-PM001A-EN-P - November 2005
A-4 Programming Software Versions, Compatibility, and Firmware Updates
Firmware and Software Version Compatibility
The following table shows the best choice combinations of GuardPLC
controller and distributed I/O firmware and RSLogix Guard PLUS!
software versions. When other combinations are used, you will not
have access to certain functional upgrades.
CPU/COM
Version
GuardPLC
Controller
Platform
Distributed
I/O Firmware
Version
RSLogix Guard PLUS!
Software Version
Compatible?
CPU 1.04
COM 1.00
1200 and 2000
N/A
3.3
Yes
3.5 and above
No
CPU 2.04
COM 2.80
1200 and 2000
N/A
3.3
Yes
3.5 and above
No
CPU 4.32
COM 4.24
1200 and 2000
4.28
3.5 and above
Yes
CPU 4.32
COM 5.14
1600 and 1800
4.28
3.5 and above
Yes
CPU 4.32
COM 4.24
1200 and 2000
6.12 and above
3.5 and above
No
CPU 4.32
COM 5.14
1600 and 1800
6.12 and above
3.5 and above
No
CPU 6.12
COM 8.32
1200, 2000,
1600 and 1800
4.28
3.5 and above
Yes
(1)(2)
(1) We recommend upgrading your CPU firmware to version 6.28.
(2) We recommend upgrading your distributed I/O firmware to version 6.28.
CPU 6.12
COM 8.32
1200, 2000,
1600 and 1800
6.12
3.5 and above
Yes
CPU 6.12
COM 8.32
1200, 2000,
1600 and 1800
6.28
3.5 and above
Yes
CPU 6.28
COM 8.32
1200, 2000,
1600 and 1800
4.28
3.5 and above
Yes
CPU 6.28
COM 8.32
1200, 2000,
1600 and 1800
6.12
3.5 and above
Yes
CPU 6.28
COM 8.32
1200, 2000,
1600 and 1800
6.28
3.5 and above
Yes
CPU 6.28
COM 10.36
1600 and 1800
6.12
3.5 and above
Yes
CPU 6.28
COM 10.36
1600 and 1800
6.28
3.5 and above
Yes