Change the srs of the controller, Change the srs of the controller -22 – Rockwell Automation 1753-PCS-PAR Using RSLogix Guard PLUS! with GuardPLC Controllers User Manual
Page 32

Publication 1753-PM001A-EN-P - November 2005
1-22 Connect to the GuardPLC Controller
Change the SRS of the
Controller
There are two ways to change the SRS of the controller:
From the Control Panel:
1. Choose Change System ID (SRS) from the Extra menu.
2. Enter the SRS.
3. Click OK.
Or follow Step 4: Get Communication Settings on page 1-9 and
Step 5: Change Settings via MAC Address on page 1-10.
TIP
If communication fails:
• check to make sure you entered the address
correctly.
• check that your PC is configured properly.
• anti-virus or firewall programs have blocked
communications.
• the cable is not connected or is not the correct
cable.
– A GuardPLC 1600 or 1800 controller can use
direct or cross-over cable.
– A GuardPLC 1200 or 2000 controller can use a
cross-over cable connected directly from a PC
to the controller or direct cables connected to
a switch or hub.
• your hardware (either the controller or the PC) is
not working.