2-2 Connect to GuardPLC Distributed I/O Modules
Distributed I/O modules inherit the first portion of the SRS from the
parent controller. You configure the second part of the SRS. For
example, the default SRS of distributed I/O modules is 60000.1. If the
module is owned by a controller with an address of 25, then the SRS
of the distributed I/O should be 25.1. If a second module is added to
the controller, its SRS is then 25.2. A third module would be SRS 25.3.
IP Address
Like any Ethernet device, the distributed I/O module requires a
unique IP address.
Add the Module
to the
Hardware Configuration
To add a distributed I/O module to your GuardPLC project’s hardware
configuration:
1. In the Hardware Management window of RSLogix Guard PLUS!,
right-click the Distributed I/O folder under your controller
Resource.
2. Choose New and the desired I/O module.
The Specify HH Network dialog appears. Because the controller
and the distributed I/O modules communicate via GuardPLC
Ethernet, you must specify a GuardPLC Ethernet network.