B-4 Quick Start For the 1738-ADNX
RSNetWorx will go on line. A screen similar to the one below
will appear:
8.
After the browse is complete, from the RSNetWorx for
DeviceNet main menu select File>Save As.
9. Type in MainNetworkADNX as the filename (use this exact
name to avoid confusion later).
10. Click Save.
On the main network, the 1738-ADNX acts as an adapter.
• The rotary switches on the front of the 1738-ADNX should be set
to node 16.
• Verify your browse reported the 1738-ADNX at node 16.
• Later you will browse deeper to see the Subnet. (Note that on
the Subnet, the 1738-ADNX acts as a scanner and is always at
node 0 on that network.)
11. Download a blank scanlist to the 1756-DNB.
a. You do not want the existing program in our Logix processors
to interfere with clearing the scanlist. To ensure that this does
not occur, use the key switch to put all the processors in
program mode then back to remote program (turn the keys
right then back to the middle position).
b. Double click the 1756-DNB to bring up its properties page.
Your system may not look like the above system. (You may have more nodes.) It is only
important to verify that you have the 1756-DNB at node 0 and the 1738-ADNX at note 16.