Control terminal designations – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual
Page 66
![background image](/manuals/578372/66/background.png)
56
Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
Chapter 2
Installation
Control Terminal
Designations
, the SMC Flex controller contains 24 control terminals on
the front of the controller.
Figure 35 - SMC Flex Controller Control Terminals
Note: The OFF state leakage current for a solid-state device connected to an SMC Flex input must be less than 6 mA.
Terminal
Number
Description
Terminal
Number
Description
11
Control Power Input
(1)
(1) RC snubbers are required on inductive loads connected to auxiliary.
23
PTC Input
12
Control Power Common
24
PTC Input
13
Control Enable Input
(2)
(2) Do not connect any additional loads to these terminals. These “parasitic” loads may cause problems with operation, which may
result in false starting and stopping.
25
Tach Input (-)
14
Control Module Ground
26
Tach Input (+)
15
Option Input #2
27
Ground Fault Transformer Input
16
Option Input #1
28
Ground Fault Transformer Input
17
Start Input
29
Aux. Contact #2
18
Stop Input
30
Aux. Contact #2
19
Aux. Contact #1 (Ext. Bypass)
(3) Aux. Contact #1 is always programmed for Ext. Bypass (NO) to control the bypass contactor in MV applications.
31
Aux. Contact #3
20
Aux. Contact #1 (Ext. Bypass)
32
Aux. Contact #3
21
Not Used
33
Aux. Contact #4 (Normal)
(1)(4)
(4) Aux Contact #4 is always programmed for “Normal” (NO) to control the isolation contactor in MV applications.
22
Not Used
34
Aux. Contact #4 (Normal)