Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual
Page 102
92
Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
Chapter 6
Options
Option
Parameter
Range
Braking Control
(1)
(cont.)
(1) Braking Control is not offered for standard use in MV applications. Please consult factory for further assistance.
Accu-Stop
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Braking Control
Slow Speed Select
Allows the user to program the slow
speed that best fits the application.
Low: 7%
High:15%
Slow Accel Current
Allows the user to program the
required current to accelerate the
motor to slow speed operation.
0 to 450% of full load current
Slow Running Current
Allows the user to program the
required current to operate the motor
at slow speed operation.
0 to 400% of full load current
Braking Current
(2)
Allows the user to program the
intensity of the braking current
applied to the motor.
(2) All braking/stopping current settings in the range of 1…100% will provide 100% braking current to the motor.
0 to 400% of full load current
Stopping Current
Allows the user to program the
intensity of the braking current
applied to the motor from slow speed
operation.
0 to 400% of full load current
Slow Speed with Braking
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Braking Control
Slow Speed Select
Allows the user to program the slow
speed that best fits the application.
Low:7%
High: 15%
Slow Accel Current
Allows the user to program the
required current to accelerate the
motor to slow speed operation.
0 to 450% of full load current
Slow Running Current
Allows the user to program the
required current to operate the motor
at the slow speed setting.
0 to 450% of full load current
Braking Current
Allows the user to program the
intensity of the braking current
applied to the motor.
0 to 400% of full load current