Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual
Page 173

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
163
Parameter Information
Appendix B
Group
Parameter Description
Parameter
Number
Units
Min / Max
Default
Settings
User
Settings
Linear List
Fault 1
124
0…255
Fault 2
125
0…255
Fault 3
126
0…255
Fault 4
127
0…255
Fault 5
128
0…255
Basic Set Up
Option 1 Input
132
Disable
Stop Option
Fault
Fault NC
Network
Stop
Option
Stop Input
133
Coast
Stop Option
Coast
Tuning and Special Parameters
(Visible with 6.001 and later firmware.)
(Visible and writable only with Password
1196 on 5.00n and earlier firmware.)
Pump Pedestal
34
%
0…50
0
(2)
Braking Time
36
Sec
0…999
0
(3)
Load Type
37
Standard
High Inertia
High Friction
Ramp 89
Standard
High Eff. Brake
38
%
0…99
0
OL Shunt Time
48
Sec
0…999
0
OL Trip Enable
49
Disable
Enable
Enable
Line Fault
84
Disable
Disable F1
Disable F41
Enable
Enable
Emergency Run
85
Disable
Enable
Disable
Current Loss
86
Disable
Enable
Enable
Timed Start
112
Disable
Enable
Disable
See Param.
#114
I Shutoff Level
113
%
0…37
0
Do not
change
UTS Level
114
%
0…100
75
V Shutoff Level
117
%
0…100
25
OL Reset Level
118
%
0…99
75
Ambient Temp.
119
0…60
50
Do not
change
Notch Position
120
%
40.0…100.0
87.5
Do not
change
Notch Maximum
121
50…70
70
Do not
change
Start Delay
122
Sec
0…30
0
Bypass Delay
123
Sec
0…15
0
Start Time E
129
Sec
0…999
0
Start Time E2
130
Sec
0…999
0
Stop Time E
131
Sec
0…999
0
Elapsed Time 2
134
Hours
0…3000
(1)
(1) Read-only parameter
(2) Pump modules only
(3) Brake modules only