beautypg.com

Step 7 – additional mounting support, Tions (refer to, Step 7 – additional mounting – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 204

background image

194

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Appendix E

ArcShield Plenum Installation Instructions

STEP 7 – Additional
Mounting Support

The Extension/Elbow Assembly must have additional mounting support.

90° Elbow Section:

Approximate weight 64 kg (142 lbs)

36" Extension Assembly:

Approximate weight 51 kg (112 lbs)

Figure 100

shows an example of how the Extension/Elbow Sections can be

supported by suspension from a high ceiling. Points A, B & C show where chains
or high tension cables may be connected.

Figure 100 - Completed Assembly for optional vertical exit Plenum (Right hand exit)

A

B

C

TIP

During an arc fault, the plenum will be subjected to a brief high pressure shock
wave. The Extension/Elbow assembly may experience dynamic loading. It is
important to account for dynamic loading when selecting supporting means
and materials.