Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual
Page 162
![background image](/manuals/578372/162/background.png)
152
Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
Appendix A
Specifications
Short Circuit Protection
The power electronics unit must be protected by current-limiting fuses (to be included by customer in existing starter with 1560E). The combination controller includes appropriate
fusing (coordinated with motor).
Fault Level Withstand as a Fused (E2) Controller NEMA E2
5000 V
350 MVA Sym
7200 V
500 MVA Sym
Control Circuit
Rated Operation Voltage
120/240 V AC (-15%, +10%)
110/230V ~ (-15%, +10%)
Dielectric Withstand
1600 V AC
2000 V ~
Operating Frequency
50/60 Hz
50/60 Hz
Enclosure
Enclosure Type
NEMA Type 1, 1G, 12 and 3R
IP 10, 21, 52 and 34
Overload Characteristics (Control Module)
Type
Solid-state thermal overload with phase loss
Current Range
1.0 – 2200 Amps
Trip Classes
10, 15, 20 and 30
Trip Current Rating
120% of Motor FLC
Number of Poles
3
Power Requirements
Control Module
75 VA
Gate Driver Boards
Self-powered
(1)
Contactor
See Contactor Specifications
Auxiliary Contacts (Control Module)
Rated Operation Voltage (Max.)
20-265 V AC
5-30 V DC (resistive)
20-265 V ~
5-30 V DC (resistive)
Rated Insulation Voltage
N/A
277 V ~
Operating Frequency
50/60 Hz, DC
50/60 Hz, DC
Utilization Category
B300
30 VDC @ 0.88A pilot duty
AC-15
DC-12
Mechanical Ratings (Control Module)
Terminals
Control Terminals :
M 3.5 x 0.6 Pozidriv screw with self-lifting clamp plate
SCPD Performance
Type 2
SCPD List
Class CC 8A @ 1000 A Available Fault Current
DPI Communication (Control Module)
Maximum Output Current
280 mA
Metering Functionality (Control Module)
Voltage, Current, MW, MWh, Displacement Power Factor
Yes
Tachometer Input (Control Module)
Voltage
0 – 4.5 VDC
Current
1.0 mA
(1) For stop maneuvers, the gate driver boards are pre-charged with a current loop power supply (30 VA).
Electrical Ratings
UL/CSA/NEMA
IEC