Snubber and resistor circuit testing – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual
Page 147
![background image](/manuals/578372/147/background.png)
Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013
137
Troubleshooting
Chapter 9
Snubber and Resistor Circuit
Testing
If the resistance checks from the Thyristor testing section were abnormal and the
thyristors checked out OK, there may be a problem in the snubber or resistor
circuits.
1.
Remove all power from the equipment.
2.
Check the snubber components and sharing resistors by isolating them and
measuring values as follows (See
to
):
RS
60Ω (180A and 360A)
30Ω (660A)
CS
0.5 or 0.68 μF (180A and 360A)
1.0
μF (600A)
RRx
32.5 kΩ total, taps at 2.5 kΩ from each end
(x = 1, 2 or 3)
Replace any out-of-spec components. See
3.
If the snubbers and sharing resistors are within tolerances, check the
resistance of the voltage sensing module (refer to
). Remove the
ribbon connector from J1 by pressing down on the locking tabs then gently
pulling the connector out. Take note of which tap the white high voltage
wires are connected to, then remove them (L1, T1, L2, T2, L3, T3).
Measure the resistance between each tap and the ground connection, and
compare to the values in
.
SHOCK HAZARD: To avoid shock hazard, ensure main power has been
disconnected before working on the controller, motor or control
devices. Verify that all circuits are voltage free using a hot stick or
appropriate voltage measuring device. Failure to do so may result in
burns, injury or death.