Power Terminal Block
Power Terminal Block Specifications
Power Wiring
Power Wire Rating
Recommended Copper Wire
Unshielded 600V, 75°C (167°F) THHN/THWN
15 Mils insulated, dry location
Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/
RHW-2
Anixter OLF-7xxxxx,
Belden 29501-29507 or
equivalent
Shielded Tray rated 600V, 75°C or 90°C (167°F or
194°F) RHH/RHW-2
Anixter 7V-7xxxx-3G
Shawflex 2ACD/3ACD or
equivalent
Terminal
(1)
Description
R/L1, S/L2
1-Phase Input
(2)
R/L1, S/L2, T/L3 3-Phase Input
U/T1
To Motor U/T1
=
Switch any two motor
leads to change
forward direction.
V/T2
To Motor V/T2
W/T3
To Motor W/T3
P2, P1
DC Bus Inductor Connection (C Frame drives only.)
The C Frame drive is shipped with a jumper between
Terminals P2 and P1. Remove this jumper only when a DC
Bus Inductor will be connected. Drive will not power up
without a jumper or inductor connected.
DC+, DC-
DC Bus Connection
BR+, BR-
Dynamic Brake Resistor Connection
Safety Ground - PE
(1)
Important:
Terminal screws may become loose during shipment. Ensure that all
terminal screws are tightened to the recommended torque before applying power to
the drive.
(2)
Single-phase operation requires a 65% derate of drive rated current.
Frame
Maximum Wire Size
(1)
Minimum Wire Size
(1)
Torque
B
5.3 mm
2
(10 AWG)
1.3 mm
2
(16 AWG)
1.7-2.2 N-m (16-19 lb.-in.)
C
8.4 mm
2
(8 AWG)
1.3 mm
2
(16 AWG)
2.9-3.7 N-m (26-33 lb.-in.)
(1)
Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.
V/T2
T/L3
S/L2
R/L1
U/T1
W/T3
BR+
BR-
DC- DC+
V/T2
T/L3
S/L2
R/L1
U/T1
W/T3
P2
P1
BR+
BR-
DC- DC+
B Frame
C Frame