English-7

Power Terminal Block

Power Terminal Block Specifications

Power Wiring

Power Wire Rating

Recommended Copper Wire

Unshielded 600V, 75°C (167°F) THHN/THWN

15 Mils insulated, dry location

Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/

RHW-2

Anixter OLF-7xxxxx,

Belden 29501-29507 or

equivalent

Shielded Tray rated 600V, 75°C or 90°C (167°F or

194°F) RHH/RHW-2

Anixter 7V-7xxxx-3G

Shawflex 2ACD/3ACD or

equivalent

Terminal

(1)

Description

R/L1, S/L2

1-Phase Input

(2)

R/L1, S/L2, T/L3 3-Phase Input
U/T1

To Motor U/T1

=

Switch any two motor

leads to change

forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

P2, P1

DC Bus Inductor Connection (C Frame drives only.)
The C Frame drive is shipped with a jumper between

Terminals P2 and P1. Remove this jumper only when a DC

Bus Inductor will be connected. Drive will not power up

without a jumper or inductor connected.

DC+, DC-

DC Bus Connection

BR+, BR-

Dynamic Brake Resistor Connection
Safety Ground - PE

(1)

Important:

Terminal screws may become loose during shipment. Ensure that all

terminal screws are tightened to the recommended torque before applying power to

the drive.

(2)

Single-phase operation requires a 65% derate of drive rated current.

Frame

Maximum Wire Size

(1)

Minimum Wire Size

(1)

Torque

B

5.3 mm

2

(10 AWG)

1.3 mm

2

(16 AWG)

1.7-2.2 N-m (16-19 lb.-in.)

C

8.4 mm

2

(8 AWG)

1.3 mm

2

(16 AWG)

2.9-3.7 N-m (26-33 lb.-in.)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not

recommendations.

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

P2

P1

BR+

BR-

DC- DC+

B Frame

C Frame