L-force controls | i/o system 1000, Networking via can system bus port assignment – Lenze L-force I/O System 1000 User Manual
Page 73

2.0 EN - 11/2010
L
73
L-force Controls | I/O System 1000
Networking via CAN system bus
Port assignment
Ticker value: After mains connection a ticker is started, which after 65535 s starts with 0
again. With every change of the count value, the ticker value (16 bit) and the count value
are stored in the input area.
1)
The bits are set until reset with RES_SET (bit 6 control word).
EPM-S600
Status word
Bit
Designation
Function
0
STS_SYNC
Reset was active
1
STS_CTRL_DO
Is set if the digital output is enabled
2
STS_SW-GATE
Software gate status (set if SW gate active)
3
STS_RST
Status of reset input
4
STS_STRT
Hardware gate status (set if HW gate active)
5
STS_GATE
Status of internal gate (set if internal gate active)
6
STS_DO
Status of digital counter output (DO)
7
STS_C_DN
Status set for counter direction backwards
8
STS_C_UP
Status set for counter direction forwards
9
STS_CMP
1)
Comparator status is set if the comparison condition is met.
If the comparison is deactivated (counter mode byte 1 = 000
b
), the
bit has no function.
10
STS_END
1)
Status set if final value was reached
11
STS_OFLW
1)
Status set in the case of overflow
12
STS_UFLW
1)
Status set in the case of underflow
13
STS_ZP
1)
Status set in the case of zero crossing
14
STS_LTCH
Status of latch input
15
–
Reserved
EPM-S600
Control word
Bit
Designation
Function
0
CTRL_SYNC_SET
Activates the reset mode
1
CTRL_DO_SET
Enables the digital output
2
SW_GATE_SET
Sets the software gate
3
–
Reserved
4
–
Reserved
5
COUNTERVAL_SET
Sets the counter temporarily to the value in the set value
6
RES_SET
Resets the following bits with a 0-1 edge:
STS_CMP, STS_END, STS_OFLW, STS_UFLW and STS_ZP
7
–
Reserved
8
CTRL_SYNC_RESET
Deactivates the reset mode
9
CTRL_DO_RESET
Inhibits the digital output
10
SW_GATE_RESET
Resets the software gate
11 ... 15
–
Reserved