4 electronic module - analog input, 1 "aix 12bit" and "aix 16bit" electronic modules, Aix 12bit" and "aix 16bit" electronic modules – Lenze L-force I/O System 1000 User Manual
Page 43: Electronic module - analog input ( 43), Electronic module - analog input, L-force controls | i/o system 1000

2.0 EN - 11/2010
L
43
L-force Controls | I/O System 1000
Parameter setting
Electronic module - analog input
6.4
Electronic module - analog input
6.4.1
"AIx 12Bit" and "AIx 16Bit" electronic modules
Use the Parameters tab to select the settings for the electronic module. In addition, the
channel status is indicated.
How to parameterise the electronic module:
1. Select the electronic module in the project view.
2. Click the Parameters tab in the workspace.
3. Make settings for each channel.
Legend
Description
Index
Accept module
parameter
Changed settings will not be accepted until the function has been executed.
Click the input field to open the drop down menu.
• 255: Accept module parameters
0x31FF
Channel status
Display of the current input signal of 0 ... 10 V.
0x6401
Signal function
Signal function of the channel.
Click the input field to open the drop down menu.
• 16: 0...10V /0...27648dec
–Voltage measurement of 0 ... 10 V and a resolution of 0 ... 27648.
–The value range is displayed in the object.
• 32: 0...10V /0...16384dec
–Voltage measurement of 0 ... 10 V and a resolution of 0 ... 16384.
–The value range is displayed in the object.
• 255: Channel deactivated
–No voltage measurement
0x31xx