beautypg.com

7 test voltages according to en 60730, part 1, Test voltages according to en 60730, part 1, Electrical safety – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 92: Environmental influences, 8 technical data

background image

8 Technical data

2014-05-01

92

8.7

Test voltages according to EN 60730, part 1

8.8

Electrical safety

8.9

Environmental influences

Input and output against voltage supply
- At a voltage supply AC 110 to 240 V +10 % /-15 %

3.7 kV/50 Hz

- At a voltage supply AC/DC 20 to 30 V, 48 to 63 Hz

3.7kV/50 Hz

Clearances / creep paths

Mains to electronic components

and probes

6 mm

/ ≥

8 mm

Mains to relays

6 mm

/ ≥

8 mm

Relays to electronic components

and probes

6 mm

/ ≥

8 mm

Electrical safety

According to DIN EN 14597 (DIN EN 60730-2-9)

Overvoltage category III, pollution degree 2

Protection rating I

With internal separation from SELV current circuits

Ambient temperature range

0 to. +55 °C

Storage temperature range

-30 to +70 °C

Temperature influence

±

0.005 % / K dev. from 23 °C

1

for RTD temperature probes

± 0.01% / K dev. from 23°C

1

for thermocouples and current

Environmental performance

85 % rel. humidity without condensation

(3K3 with extended temperature range according to DIN EN 60721-3-3)