6 Safety Manual

47

2014-05-01

Safety feature

Requirement / comment

SIL

The sensor system is included in the

SIL evaluation.

SIL2

SIL3

Operating mode concerning

safety function

Operating mode with lower and higher demand rate possible on a customer-specific

basis

Safety-critical inputs

Temperature sensor inputs 4 to 20 mA current loop

Safety-relevant inputs

Setup and parameterization

Safety-critical output

Alarm contact limit value

Subsystem type

Type B

Safety architecture (logic unit JUMO

STB/STW 701150)

1oo2D

Safety architecture (sensor system)

SIL2

1oo1

SIL3

1oo2

Hardware error tolerance (logic unit

JUMO STB/STW 70.1150)

HFT=1

Hardware error tolerance (sensor sys-

tem)

SIL2: HFT=0

SIL3: HFT=1

Proportion of safe errors

SIL2 sensor system HFT=0: 90 % to < 99 % SIL3 sensor system HFT=1:

90 % to <99 %

CCF

Calculation according to DIN EN 61508 Part 7 Appendix D and/or DIN EN ISO 13849-

1 Table F.1 min. 65 %

Average failure probability of a safety

function on demand (overall system)

SIL2:

Low demand: PFD

avg

< 10

-2

High demand: PFH < 10

-6

SIL3:

Low demand: PFD

avg

< 10

-3

High demand: PFH < 10

-7

Interval for repeat test

No repeat test