beautypg.com

11 error messages, Error messages – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 102

background image

11 Error messages

2014-05-01

102

11 Error

messages

These error messages are displayed one below the other.

Error display (Err)

Origin

Cause/remedy

Internal

The set limit value for relay switching operations has been reached

h

Increase the limit value for the relay switching operations

v

Chapter 7.7.1 "Limit switching cycle"

A tick appears in place of the bell and the error message can be acknowl-

edged

Terminal temp.

Internal

The internal Pt100 is defective

1

, or the terminal temperature has fallen out-

side the admissible range (-10 to 80 °C).

This error cannot be acknowledged until it is within the admissible range

again.

Reference volt.

1

Internal

The reference voltage is outside the valid range.
Acknowledgement is not possible until it is within the valid range again.

Calibration const.

1

Internal

A calibration constant is outside the valid range.
Acknowledgement is not possible until it is within the valid range again.

Configuration

Internal

Configuration data outside the value range.
Acknowledgement is not possible until it is within the valid range again.

Measured value

Internal

The measured value 1 or 2 is outside the valid range.
Acknowledgement is not possible until it is within the valid range again.