4 Electrical connection

25

2014-05-01

4 to 20 mA

V

4 to 20 mA for both analog inputs

Caution:

When only one probe (SIL2) is connected, the temperature limitation device

is reduced from SIL3 to SIL2. However, the internal 2-channel structure (1oo2D) in the device is still retained.

Both channels measure the same current signal due to the simplified external circuit.

4

Binary input

Connection to a potential-free contact

5

Analog output:

0 to 20 mA

4 to 20 mA (ex-factory)

0(2) to 10V

V

Caution
The analog output is not part of the safety func-
tion!

9

Voltage supply

according to rating plate

AC:

L1 Line conductor

N Neutral

DC:

(L+)

(L-)