7 Configuration level

87

2014-05-01

7.7

Service

Parameter

Comment

Value range
(factory-setting in bold)

7.7.1

Limit switching cycle

Limit value for relay switching cycles

Here, the limit value for the admissible relay switching

cycles is set.

If the counter value for Current switching cycles is

greater than this value, the display values flash and the

alarm relay output secedes.
If "0" is set the function is inactive.

0

to 99999

7.7.2

Current switching cycles

Relay switching cycle counter
Here, the switching cycles for the relay are only count-

ed if the top limit value for relay switching cycles is

not set to "0" and is thus inactive.
The value can then be adjusted as required and there-

fore adapted accordingly to the plant.

The switching cycle counter remains at 99999.

0

to 99999

7.7.3

Operating hours

Operating hour counter
The counter adds up the operating hours during which

the device was connected to the voltage supply.
The value cannot be changed and can be used as a

measure of how long the device was actually in opera-

tion after leaving the plant.

0

to 99999