7 Configuration level

2014-05-01

76

7.3

Limiter/monitor

Parameter

Comment

Value range
(factory-setting in bold)

7.3.1

Device function

Safety temperature limiter (STB) initial startup:

Regardless of the switching status of the alarm relay

output prior to power failure, the STB remains locked

when power returns.
The purpose of this factory setting is to ensure that the

device will be in a safe switched-off state when the

voltage supply is switched on for the first time.

After this initial startup, the device function can be set

to STB or STW.

STB initial startup,

STB,

STW

Safety temperature limiter STB:
The device must be manually reset using the keypad or

the binary input as soon as the main measured value is

back within the valid range.
Safety temperature monitor STW
The device is automatically reset as soon as the main

measured value is back within the valid range.