6 Safety Manual

53

2014-05-01

6.11.1

Calculations DIN EN ISO 13849-1 Performance Level - low voltage 230 V

6.11.2

Calculations DIN EN ISO 13849-1 Performance Level - extra low voltage (ELV) 24 V

Variant

MTTF

d

DC

avg

CCF

PL

1

100 years

3

(337 years)

90 %

80

PLd

1a

100 years

3

(337 years)

90 %

80

PLe

2

100 years

3

(340 years)

90 %

80

PLe

3

100 years

3

(317 years)

91 %

80

PLe

4

100 years

3

(313 years)

91 %

80

PLe

5

100 years

3

(327 years)

91 %

80

See above table

Variant

MTTF

d

DC

avg

CCF

PL

1

100 years

3

(336 years)

90 %

80

PLd

1a

100 years

3

(336 years)

90 %

80

PLe

2

100 years

3

(339 years)

90 %

80

PLe

3

100 years

3

(315 years)

90 %

80

PLe

4

100 years

3

(311 years)

90 %

80

PLe

3.

The MTTF

d

value of a partial system must be

limited to 100 years according to the DIN EN
ISO 13849-1 requirements.

5

100 years

3

(318 years)

90 %

80

See above table