12 What to do, if ...

107

2014-05-01

12

What to do, if ...

Description

Cause

Remedy

The following appears in

the display:

Setup program transmits data.

The monitoring function switches off briefly dur-

ing data transmission and the device re-starts.

-

Wait until data transmission has finished.

The

measured

value

flashes in the top display.

The device is in the alarm range

LEDs K1, K2 are lit red.

The measured value flashes in the display and is

higher or lower than the limit value depending on

the switching behavior set.
-

Measured value too high or too low

-

Excessive deviation between the

temperature values during difference moni-

toring

h

Check the limit value in the configuration

level.

h

Find out the reason for the overrange or un-

derrange.

h

If necessary, correct the limit value

h

If necessary, reduce an excessive hysteresis

because it might be too high in the OK

range.

v

Chapter 7.7.3 "Operating hours"

LED K1 is lit red,

although the measured

value is in the OK range

The device is set as a safety temperature lim-
iter (STB).
Even if the measured value is already in the OK

range after being exceeded, the relay of an auto-

matic reset temperature limiter does not auto-

matically reset.

It must be unlocked manually.

h

Press the

key for longer than 3 seconds

to manually unlock the relay.

v

Chapter 5.5 "Alarm acknowledgement

using the Reset key (only for temperature

limiters STB)"