10 Alarm messages

101

2014-05-01

10 Alarm

messages

They can appear as follows:

Alarm display

Cause

Remedy

5 flashing horizontal lines: Measured value error

No valid value can be displayed

h

Check error messages on the screen

h

Please contact the JUMO Service department

v

Chapter 2.4 "Service addresses"

Measured value overrange

The measured value is too high, is out-

side the measuring range or the probe

is broken.

h

Change the display to 2 measured values

This makes it possible to detect which channel is de-

fective.

h

Check the probe and connection line for damage or

short-circuit.

v

Chapter 4.2 "Connection diagram"

h

Check that the correct probe is set and/or connect-

ed.

v

Chapter 7.2 "Analog inputs"

Measured value underrange

The measured value is too low, is out-

side the measuring range or a short-cir-

cuit occurred at the probe.

5 flashing asterisks

Display overflow

Value cannot be displayed

h

Check error messages on the screen

h

Please contact the JUMO Service department

v

Chapter 2.4 "Service addresses"