beautypg.com

12 what to do, if – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 108

background image

12 What to do, if ...

2014-05-01

108

Description

Cause

Remedy

... relay output "Alarm"

between terminal 14 and

16 is not closed although

the LED OK is lit green (in

the OK range).

-

The integrated fuse cut-out is defective,

caused by an excessive relay current.

h

Measure terminal 14 and 16 of the relay

when the LED K1 is lit green using a conti-

nuity test device.

h

The device must be returned to JUMO for

repair.

v

Chapter 2.4 "Service addresses"

... the display is dark,

only the LEDs are lit

-

Display shut-down after timeout was activat-

ed

h

Press any key

or switch off timeout.

v

Chapter 7.6.8 "Time-out operation"