6 Safety Manual

2014-05-01

36

The possibility to connect passive sensors such as double thermocouples, Pt100 sensors, or Pt1000 sensors means that the

sensors do not necessarily require a SIL qualification. In this case, the specification of the failure rates for the passive sensors

is sufficient for the SIL qualification of the overall system. The user of the system must always determine the PFD

avg

and/or

PFH value of the overall safety chain to evaluate the achieved SIL
Requirements regarding proof-check interval and lifetime apply only in terms of functional safety.
Requirements as specified by DIN EN 14 597 are defined in the Operating Manual B 701150 and are independent of the re-

quirements of this Safety Manual.

Temperature probe

Admissible measuring ranges must be observed for devices with approval according to DIN EN 14 597 and SIL certification. If

other temperature probes than those described by JUMO data sheets 901006 and 902006 are used, their registration and suit-

ability for use must be verified.