Max. alarm:

If the measured value exceeds the limit value, the alarm

relay output switches OFF. The LEDs K1 and K2 light

up red and the measured values flash in the display.

If set to the safety temperature limiter (STB) setting, this condition remains even when the main

measured value is back in the valid range. Only when the "Reset" key is pressed or a switch is

activated when the binary input is respectively configured will the alarm relay output switch on

again and the OK LED light up green.

When setting the safety temperature monitor (STW), the alarm relay output automatically

switches back to ON as soon as the main measured value is back within the valid range.

Parameter

Comment

Value range
(factory-setting in bold)

Limit value

S

P

14

16

15

Ö

3,15A

S

P

14

16

15

Ö

3,15A

Min. set.range

Max. set.range

Hyster

esis

Relay output Alarm aktive

Relay output Alarm inactive

S

P

11

12

13

Ö

Max. alarm

(older devices: inverse or O-Function)

Distance from limit value

Pre-alarm range

Measured value

Measured value

Alarm range

Valid range

Pre-alarm (absolute value)

Hyster

esis

Relay output pre-alarm

active

KV

Relay output pre-alarm
KV inactive

LED KV lights up yellow

LED OK lights up green

LED K1, K2 lights up red