beautypg.com

2 analog inputs, Analog inputs, 1 connection – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 71: 7 configuration level

background image

7 Configuration level

71

2014-05-01

7.2

Analog inputs

k

Factory setting

7.2.1

Connection

Comment

Two sensors

This setting is provided for dual probes or for two different probes.

Each of the two analog inputs is monitored separately for probe break, probe

short-circuit.

Single Pt100 in 2-wire circuit

V

Caution:

When only one probe (SIL2) is connected, the temperature limiter device is

reduced from SIL3 to SIL2!

However, the internal 2-channel structure (1oo2D) in the device still remains.

Both channels measure the same sensor due to the simplified external wiring.

Single 4 to 20 mA

V

Caution:

When only one probe (SIL2) is connected, the temperature limiter device is

reduced from SIL3 to SIL2!

However, the internal 2-channel structure (1oo2D) in the device still remains.

Both channels measure the same current signal due to the simplified external

wiring.