beautypg.com

2 safety-relevant system properties, 6 safety manual – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 46

background image

6 Safety Manual

2014-05-01

46

6.9.2

Safety-relevant system properties

Device versions differ in the following architectures:
The evaluation unit from 701150 in STW, STB versions is implemented as 1oo2D architecture.
The types with an individual sensor are executed in one-channel sensor systems (1oo1).

The variants with two sensors are consistently structured with two channels.

The two subsystems have to be galvanically isolated from each other.

Systems have a lifetime of ten years.
The proof check for SIL2 and SIL3 certified systems is also ten years.
If the temperature is above/below the permissible limits, the system switches to the safe state without delay. Premature switch-

ing is admissible if a malfunction is detected.

These are monitored:
-

Probe break in the sensor system subsystem

-

Probe short circuit in the sensor system subsystem

-

Random hardware failure in one channel

These are monitored:
-

Probe break sensor system subsystem

-

Probe short circuit in the sensor system subsystem

-

Reverse polarity of the probes

-

Random hardware failure in one channel