14 Output behavior

2014-05-01

112

Operating status

Relay output alarm

Relay output
pre-alarm KV

Analog output

Initialization

Initialization phase after mains voltage – ON
(for approx. 10 seconds)

Inactive

Inactive

0 mA,
0 V

Setup communication

During reading-writing of the configuration
(for approx. 5 seconds)

Inactive

Pre-alarm moni-

toring active

v

Chapter

7.3.4

Scaled analog signal is

being output

v

Chapter 7.5

Standard operation

After initialization phase system is in error-free
status

(STB - initial startup)

Inactive
Unlocking possible

Pre-alarm moni-

toring active

v

Chapter

7.3.4

Scaled analog signal is

being output

v

Chapter 7.5

After initialization phase system is in error-free status
(STB, STW)

Monitoring of the limit

value active

v

Chapter 7.3.2

External error

Probe break, probe short circuit
(e.g. input 1)

Inactive

Active

v

Error signal is being

output

Chapter 7.5.5