beautypg.com

8 technical data, Technical data, Analog inputs – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 88

background image

8 Technical data

2014-05-01

88

8 Technical

data

8.1

Analog inputs

RTD temperature probe

Thermocouples

Designation Measuring

range

Accuracy
2/3-wire circuit

1

Ambient temperature
influence

Pt100

DIN EN 60751

-200 to +850 °C

0.5% / 0.1%

50 ppm/K

Pt1000

DIN EN 60751

-200 to +850 °C

0.5% / 0.1%

50 ppm/K

Connection type

2-wire, 3-wire circuit

Maximum output resistance 30

Ω

Measuring rate

210

ms

Error tolerance time

5s time taken into account for all diagnosis tests

Input filter

Digital filter, 2nd priority; filter constant can be set from 0 to 100 s

Special features

Individual probe Pt100 2-wire,

display can also be programmed in °F

Designation Measuring

range

Accuracy

1

Ambient temperature
influence

Fe-CuNi "L"

DIN 43710

-200 to +900 °C

0.4%

100 ppm/K

Fe-CuNi "J"

DIN EN 60584

-200 to +1200 °C

0.4%

100 ppm/K

Cu-CuNi "U"

DIN 43710

-200 to +600 °C

0.4%

100 ppm/K

Cu-CuNi "T"

DIN EN 60584

-200 to +400 °C

0.4%

100 ppm/K