7 Configuration level

77

2014-05-01

7.3.2

Switching behavior

Min. alarm:

If the measured value falls below the limit value, the

alarm relay output switches to OFF. The LEDs K1 and

K2 light up red and the measured values flash in the

display.

Max. alarm,

min. alarm

If set to the safety temperature limiter (STB) setting, this condition remains even when the main

measured value is back in the valid range. Only when the "Reset" key is pressed or a switch is

activated when the binary input is respectively configured will the alarm relay output switch on

again and the OK LED light up green.

When setting the safety temperature monitor (STW), the alarm relay output automatically

switches back to ON as soon as the main measured value is back within the valid range.

Parameter

Comment

Value range
(factory-setting in bold)

S

P

14

16

15

Ö

3,15A

S

P

14

16

15

Ö

3,15A

Hyster

esis

Hyster

esis

S

P

11

12

13

Ö

Min. alarm

(

direct or S-Function)

older devices:

Relay output pre-alarm

active

(KV)

Relay output pre-alarm
(KV) inaktive

Relay output alarm active

Relay output alarm inactive

Pre-alarm range

Alarm range

Valid range

Limit Value

Min. set.range

Max. set.range

Measured value

Measured value

Distance from limit value Pre-alarm (absolute value)

LED KV lights up yellow

LED K1, K2 light up red

LED OK lights up green