7 Configuration level

2014-05-01

84

7.5.6

Behavior when leaving the scaling range

The standard signal range of the analog output is limited as follows according to recommendation of Namur NE 43:

Signal type

Lower
limit

Upper
limit

0: 4 to 20 mA 3.8 mA

20.5 mA

1: 0 to 20 mA 0 mA

20.5 mA

2: 2 to 10 V

1.8 V

10.2 V

3: 0 to 10 V

0 V

10.2 V

k

Factory setting

V

Caution

The analog output is not part of the safety function!

Measured value

Standard signal

for analog output

4 mA

20 mA

3.8 mA

20.5 mA