6 Safety Manual

2014-05-01

60

-

Seals of terminal heads and cable ducts

-

Interruptions due to "knocking" on the thermometer/measuring insert

Since the maximum operating temperature influences the drift behavior, the thermometer should be recalibrated or replaced at

certain intervals to ensure reliable and precise temperature measurement.

The testing intervals are listed in the table below:

Maximum operating temper-
ature

Pt - RTD temperature probe

Thermocouples

200 °C

5 years

5 years

550 °C

2 years

5 years

700 °C

1 year

2 years

1000 °C

Non-precious metal 1

year
Precious metal 2 years

1500 °C

1 year

H

The testing intervals specified here are recommendations that must be adapted to the special conditions at the

operating location and, if necessary, the user should perform the tests more regularly.