7 Configuration level

2014-05-01

74

k

Factory setting

7.2.8

Sensor type 2

For analog input2

Comment

Setting range for limit
value:
(can be restricted via
the setup)

Limits for
Underrange /
overrange

Pt100 DIN EN 60751

In 3-wire circuit

-1999 to +9999 °C

-205 °C/ +855 °C

Pt1000 DIN EN 60751

In 3-wire circuit

-1999 to +9999 °C

-205 °C/ +855 °C

Pt100 DIN EN 60751

in 2-wire circuit

-1999 to +9999 °C

-205 °C/ +855 °C

Pt1000 DIN EN 60751

in 2-wire circuit

-1999 to +9999 °C

-205 °C/ +855 °C

W3Re-W25Re “D”

Thermocouple

-1999 to +9999 °C

-5 to +2500 °C

Cu-CuNi “T”

Thermocouple DIN EN 60584

-1999 to +9999 °C

-205 to +405 °C

Fe-CuNi “J”

Thermocouple DIN EN 60584

-1999 to +9999 °C

-205 to +1205 °C

Cu-CuNi “U”

Thermocouple DIN 43710

-1999 to +9999 °C

-205 to +605 °C

Fe-CuNi “L”

Thermocouple DIN 43710

-1999 to +9999 °C

-205 to +905 °C

NiCr-Ni “K”

Thermocouple DIN EN 60584

-1999 to +9999 °C

-205 to +1377 °C

Pt10Rh-Pt “S”

Thermocouple DIN EN 60584

-1999 to +9999 °C

-5 to +1773 °C

Pt13Rh-Pt "R"

Thermocouple DIN EN 60584

-1999 to +9999 °C

-5 to +1773 °C

Pt30Rh-Pt6Rh “B”

Thermocouple DIN EN 60584

-1999 to +9999 °C

295 to 1825 °C

NiCrSi-NiSi "N"

Thermocouple DIN EN 60584

-1999 to +9999 °C

-105 to +1305 °C

4 to 20 mA

Standard signal

-1999 to +9999 °C

3.6 to 21 mA