8 Technical data

2014-05-01

90

8.2

Analog output

8.3

Binary input

8.4

Relay outputs

Type of sig-
nal

Accuracy

Residual ripple

Load influence

Temperature

influ-

ence

Load
resis-
tance

Current

4 to 20 mA

0.5 %

± 0.5 % at 300

Ω

± 0.05 mA/ 100

Ω

150 ppm / K

500

Ω

0 to 20 mA

Voltage

2 to 10 V

0.5 %

± 0.5 %

± 15 mV

150 ppm / K

500

Ω

0 to 10 V

Connection

Function

1 potential-free contact

Unlocking, keyboard locking, level locking can be configured

Relay output KV

Relay (changeover contact) without shroud

30000 operations at a performance of 3 A /250 V, 50 Hz resistive load

or maximum DC 30 V / 3 A. Minimal current: DC 12 V / 100 mA.

Relay output alarm

Changeover contact
Contact protection switching:

safety fuse 3.15 AT, installed in the N/O contact arm

30000 operations at a performance of 3 A /230 V, 50 Hz resistive load

or maximum DC 30 V / 3 A. Minimal current: DC 12 V / 100 mA.