11 error messages – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 103

11 Error messages
103
Measured value missing
Internal
When the error status "Measured value" is signaled by the channel
then the diagnosis function tries to show the precise error on the basis of the
read measured value.
Probe short-circ.
External
Meas. range overr.
Meas. range underr.
Probe break
Operating access
1
Internal
The diagnosis function communicates with the STB/STW.
Acknowledgement is not possible until communication has finished.
Setup access
Internal
The setup program is communicating with the STB/STW.
Acknowledgement is not possible until communication has finished.
CRC calibr.
1
Internal
Checksum error of the EEPROM-calibration data.
Acknowledgement is not possible until it is within the valid range again.
CRC config.
1
Internal
Checksum error of the EEPROM-configuration data.
Acknowledgement is not possible until it is within the valid range again.
Registry
1
Internal
A registry error has occurred.
Acknowledgement not possible until the error has been remedied.
RAM defective
1
Internal
A RAM error has occurred.
Acknowledgement not possible until the error has been remedied.
ROM defective
1
Internal
A ROM error has occurred.
Acknowledgement is not possible until it is within the valid range again.
Program sequence
1
Internal
A program sequence error has occurred.
Acknowledgement not possible until the error has been remedied.
Error display (Err)
Origin
Cause/remedy