beautypg.com

11 error messages – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 103

background image

11 Error messages

103

2014-05-01

Measured value missing

Internal

When the error status "Measured value" is signaled by the channel
then the diagnosis function tries to show the precise error on the basis of the

read measured value.

Probe short-circ.

External

Meas. range overr.
Meas. range underr.
Probe break
Operating access

1

Internal

The diagnosis function communicates with the STB/STW.
Acknowledgement is not possible until communication has finished.

Setup access

Internal

The setup program is communicating with the STB/STW.
Acknowledgement is not possible until communication has finished.

CRC calibr.

1

Internal

Checksum error of the EEPROM-calibration data.
Acknowledgement is not possible until it is within the valid range again.

CRC config.

1

Internal

Checksum error of the EEPROM-configuration data.
Acknowledgement is not possible until it is within the valid range again.

Registry

1

Internal

A registry error has occurred.
Acknowledgement not possible until the error has been remedied.

RAM defective

1

Internal

A RAM error has occurred.
Acknowledgement not possible until the error has been remedied.

ROM defective

1

Internal

A ROM error has occurred.
Acknowledgement is not possible until it is within the valid range again.

Program sequence

1

Internal

A program sequence error has occurred.
Acknowledgement not possible until the error has been remedied.

Error display (Err)

Origin

Cause/remedy