7 Configuration level

2014-05-01

82

7.5

Analog output

Parameter

Comment

Value range
(factory-setting in bold)

7.5.1

Function

Here, the measured value that is to be shown at the

analog output is set.

Main measured value

Measured value1

Measured value2

Difference

Main measured value:

With the max-alarm switching behavior, the greater of

the two measured values is shown; with the min-alarm,

the lower of the two measured values is shown.

Measured value1:

Measured value of analog input 1 (E1) is shown

Measured value2:

Measured value of analog input 2 (E2) is shown

Difference:

E1-E2 is shown

The signal that should be output by the analog output

can be set with scaling start and end.

7.5.2

Signal type

4 to 20 mA

4 to 20 mA,

0 to 20 mA

2 to 10 V

0 to 10 V

0 to 20 mA
2 to 10 V
0 to 10 V

7.5.3

Scaling start

v

Picture in Chapter 7.5.6

-9999 to -200 to 9999

7.5.4

Scaling end

v

Picture in Chapter 7.5.6

-9999 to 800 to 9999