beautypg.com

Allied Telesis SwitchBlade x8112 User Manual

Page 237

background image

SwitchBlade x8112 Chassis Switch Installation Guide

237

Maximum power supply efficiency (based on 100V input voltage)

Heat dissipation (British Thermal Units/hour)

Available Power over Ethernet (Watts/port):

AT-SBx81CFC400

48.3 W

Table 29. Maximum Power Efficiency

AT-SBxPWRSYS1 AC

Up to 90%

AT-SBxPWRPOE1 AC

Up to 90%

AT-SBxPWRSYS1 DC

Up to 90%

Table 30. Heat Dissipation

AT-SBx81GT24

146.72 BTU/hr

AT-SBx81GT40

183.74 BTU/hr

AT-SBx81GP24

146.72 BTU/hr

AT-SBx81GS24a

240.13 BTU/hr

AT-SBx81XS6

233.73 BTU/hr

AT-SBx81CFC400

206.01 BTU/hr

AT-SBxPWRSYS1 AC

5118.21 BTU/hr

AT-SBxPWRPOE1 AC

5118.21 BTU/hr

AT-SBxPWRSYS1 DC

5118.21 BTU/hr

Table 31. Available Power Over Ethernet with One PoE Power Supply

One PoE Power Supply Installed

1200 W @ 56 VDC

IEEE 802.3at Class 4 (30 W /port)

40 ports Maximum

IEEE 802.3af Class 3 (15.4 W /port) 77 ports Maximum

IEEE 802.3af Class 2 (7.3 W /port) 171 ports Maximum

IEEE 802.3af Class 1 (4.0 W /port) 240 ports Maximum

Table 28. Maximum Power Consumption (Continued)