CR23X MICROLOGGER OVERVIEW

OV-20

09: P74

Minimize instruction

01:1

One

repetition

02:10

Output the time of the daily minimum in hours

and minutes

03:2

Data source is Input Storage Location 2.

The program to make the measurements and to send the desired data to Final Storage has
been entered. At this point, Instruction 96 is entered to enable data transfer from Final Storage
to Storage Module.

10:P96

Activate Serial Data Output.

1:71

Output Final Storage data to Storage Module.

The program is complete. (Here the example reverts back to the key by key format.)

Key Display Explanation

5

00:21:32 Enter

5

Mode. Clock running but perhaps not set

correctly.

A

05:0000

Advance to location for year.

1

9

9

6

05:1996

Key in year (1996).

A

05:0000

Enter and advance to location for Julian day.

1

9

7

05:197

Key in Julian day.

A

05:0021

Enter and advance to location for hours and minutes (24 hr. time).

1

3

2

4

05:1324

Key in hrs.:min. (1:24 PM in this example).

A

:13:24:01

Clock set and running.

0

Running Table 1 Exit

5

, compile Table 1, commence logging data.