SECTION 9. INPUT/OUTPUT INSTRUCTIONS

9-8

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

2

Repetitions

02:

2

Range code for
excitation
measurement (V

1

)

(Do not use autorange)
(Table 9-1)

03:

2

Range code for bridge
measurement (V

2

)

04:

2

Differential channel
number for first
measurement

05:

2

Excitation channel number
(Table 9-2A)

06:

4

Excitation voltage
(millivolts)

07:

4

Input location number
for first measurement

08:

FP

Multiplier

09:

FP

Offset

Input locations altered: 1 per repetition

*** 10 BATTERY VOLTAGE ***

FUNCTION
This instruction measures the CR23X input
voltage and writes it to an input location. The
units for voltage are volts. The measurement is
.2 to .3 volts less than actual battery voltage
measurement. See Section 14.2 for CR23X
power requirements.

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

4

Input location

Input locations altered: 1

*** 11 107 THERMISTOR PROBE ***

FUNCTION
This Instruction applies a 2.5 VAC excitation
voltage to Campbell Scientific's Model 107
Thermistor Probe, makes a slow single-ended
voltage measurement across a resistor in series
with the thermistor, and calculates the
temperature in °C with a polynomial. A
multiplier of 1 and an offset of zero yields
temperature in degrees Celsius. The maximum
polynomial error from -40°C to +56°C is given
here:

Curve Fit Error --

Range (°C)

Error (°C)

-40 to +56

<

±

1.0

-24 to +48

<

±

0.1

TABLE 9-3. Excitation/Integration Codes

Code Result

0x

excite all rep with channel x

1x

increment chan x with each rep

2x

excite all reps with channel x, slow 60 Hz
rejection, 10 ms delay

3x

excite all reps with channel x, slow 50 Hz
rejection, 10 ms delay

4x

increment chan x with each rep, slow 60 Hz
rejection, 10 ms delay

5x

increment chan x with each rep, slow 50 Hz
rejection, 10 ms delay

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

2

Repetitions

02:

2

Single-ended channel
number of first
measurement

03:

2

Excitation channel/
Integration (Table 9-3)

04:

4

Input location for first
measurement

05:

FP

Multiplier

06:

FP

Offset

Input locations altered: 1 per repetition

*** 12 207 RELATIVE HUMIDITY PROBE ***

FUNCTION
This instruction applies a 3.0 VAC excitation
across Campbell Scientific's Model 207
Temperature and RH Probe, makes a fast
single-ended measurement across a series
resistor, calculates the result with a 5th order
polynomial, and performs the required
temperature compensation before outputting
the result in % RH.

When measuring several probes, all the RH
elements should be connected sequentially.
The temperature values used to correct the RH
measurements should also be stored
sequentially to make use of the REP feature in
Instruction 11.