CR23X MICROLOGGER OVERVIEW

OV-19

An instruction is deleted by advancing to the

instruction number (P in display) and keying #D

(Table 4.2-1).

To change the value entered for a parameter,

advance to the parameter and key in the

correct value then press A. Note that the new

value is not entered until A is keyed.

SAMPLE PROGRAM 2

Instruction

Parameter

(Loc:Entry) (Par#:Entry) Description

1

Enter Program Table 1

01:60

60 second (1 minute) execution interval

Key

#

D

until

01:P00

Erase previous Program before

is displayed

continuing.

01:P17

Measure panel temperature

01:1

Store temp in Location 1

02:P14

Measure thermocouple temperature

(differential)

01:1

1

repetition

02:21

Range code (10 mV, 60 Hz Rejection)

03:5

Input channel of TC

04:1

TC type: copper-constantan

05:1

Reference temp is stored in Location 1

06:2

Store TC temp in Location 2

07:1

Multiplier of 1

08:0

No

offset

03:P92

If Time instruction

01:0

0 minutes into the interval

02:60

60 minute interval

03:10

Set Output Flag 0

The CR23X is programmed to measure the thermocouple temperature every sixty seconds.
The If Time instruction sets the Output Flag at the beginning of every hour. Next, the Output
Instructions for time and average are added.

Instruction #

Parameter

(Loc.:Entry) (Par.#:Entry) Description

04:P77

Output Time instruction

01:110

Store Julian day, hour, and minute

05:P71 Average

instruction

01:1

one

repetition

02:2

Location 2 - source of TC temps. to be

averaged

06:P92

If Time instruction

01:0

0 minutes into the interval

02:1440

1440 minute interval (24 hrs.)

03:10

Set Output Flag 0

07: P77

Output Time instruction

01:100

Store Day of Year

08: P73

Maximize instruction

01:1

One

repetition

02:10

Output time of daily maximum in hours and minutes

03:2

Data source is Input Storage Location 2.