APPENDIX B. CONTROL PORT SERIAL I/O INSTRUCTION 15

B-15

CR23X#1 PROGRAM - SEND DATA

*

1

Table 1 Programs

01:

5

Sec. Execution Interval

01:

P87

Beginning of Loop

Start loop to generate values

01:

0

Delay

02:

10

Loop Count

02:

P32

Z=Z+1

01:

11

Z Loc [:COUNTER ]

03:

P31

Z=X

01:

11

X Loc COUNTER

02:

1--

Z Loc [:VALUE #1 ]

04:

P95

End

End Loop to generate values

05:

P15

Control Port Serial I/O

01:

1

Repetitions

02:

0

Configuration code

RS-232, 1200 baud

03:

0

CTS/Delay before send

04:

15

C1 RTS/DTR, C5 TXD/RXD

DTR = C1, TX = C5

05:

1

Output start location

06:

10--

Number of locations to send

Start at Loc 10 and (--) convert

07:

0

Input termination character

08:

0

Max characters to receive

09:

100

Delay for CTS/input

wait 1 sec for CTS (C2) to go high

10:

28

First input location

If 1 sec delay expires
before CTS goes high,
store -99999 in Loc 28

11:

1

Multiplier

12:

0

Offset

06:

P

End Table 1

Input Location Labels:

1:VALUE #1

4:VALUE #4

7:VALUE #7

10:VALUE #10

2:VALUE #2

5:VALUE #5

8:VALUE #8

11:COUNTER

3:VALUE #3

6:VALUE #6

9:VALUE #9

12:_________

CR23X#2 PROGRAM - RECEIVE DATA

*

3

Table 3 Subroutines

01:

P85

Beginning of Subroutine

01:

98

Subroutine Number

02:

P15

Control Port Serial I/O

01:

1

Repetitions

02:

0

Configuration code

RS-232, 1200 bd

03:

0

CTS/Delay before send

04:

6

No RTS/DTR, C6 TXD/ RXD

05:

0

Output start location

06:

0

Number of locations to send