SECTION 9. INPUT/OUTPUT INSTRUCTIONS

9-16

3 - CS I/O port
76,800 baud to
SM192/716
5 - CS I/O port
38.4 K
6 - RS-232 port
38.4 K

D

Measurement
0 - Differential
measurement
1 - Single-ended
measurement

05:

FP

Scan interval (ms,
minimum 0.6666 x
reps, limited to 25 ms)

06:

FP

Number of scans (units
of 1000)

07:

4

Number of samples
saved before trigger (not
used with serial output)

08:

FP

Trigger limit (mV,
unscaled measurement)

09:

4

Excitation voltage (mV)

10:

4

1st input location in
which to store data

11:

FP

Multiplier (not used with
serial output)

12:

FP

Offset (not used with
serial output)

Input locations altered: number of scans plus
number of samples saved before trigger

*** 24 CALIBRATION ***

Calibrate and put calibration values into input
locations if desired. Calibration takes place only
when Instruction 24 is executed. Automatic
calibration is disabled if Instruction 24 is in a
program table. See Section 13.7 for help on
when to use Instruction 24.

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

2

Option (0 for most
applications)

02:

4

Beginning input
location (Option 0 does
not alter any input
locations)

Input Locations Used: 0 to 31 depending on
option and what is being used in the program.

TABLE 9-7

Option

Description

0

Calibrate only the active components;

do not store the results

1

Calibrate only the active components;

store the active components

2

Calibrate all components; store the

results

3

Do not calibrate; store active
components

*** 25 READ PORTS ***

FUNCTION
The status of a group of ports selected by a
mask is read and placed in an input location.
The status is a base 2 representation of the
ports converted to base 10. Port 1 is the least
significant bit. For example, if all ports are read,
and the port status is as follows:

PORT

C8

C7

C6

C5 C4 C3

C2 C1

VALUE

128

64

32

16

8

4

2

1

STATUS

0

0

1

1

0

0

1

0

(0=low,
1=high)

Base 10 equivalent: 32 + 16 + 2 = 50

50 will be stored in the input location.

The mask is also base 2 representation; 1
indicates the port is to be read, 0 results in a 0
for the port regardless of the status of the port
(AND operation). For example, if 50 (see above
example) is entered for the mask, ports 2, 5,
and 6 are read. If only ports 4 and 5 are high,
the status will be 16 (port 4 is not read).

NOTE: Voltages in excess of 16 volts
applied to a control port can cause the
CR23X to malfunction.

PARAM.

DATA

NUM.

TYPE

DESCRIPTION

01:

4

MASK (0-255)

02:

4

INPUT LOCATION TO
STORE RESULT

Input locations altered: 1