Section 10. processing instructions, 30 z = f *10n, 31 z = x – Campbell Scientific CR23X Micrologger User Manual
Page 165: 32 z = z + 1, 33 x + y, 34 x + f, 35 x - y

10-1
SECTION 10. PROCESSING INSTRUCTIONS
To facilitate cross referencing, parameter
descriptions are keyed [ ] to the values given on
the PROMPT SHEET. These values are
defined as follows:
[Z] = Destination input location for result
[X] = Input location of X
[Y] = Input location of Y
[F] = Fixed Data (user specified floating
point number)
*** 30 Z = F *10
n
***
FUNCTION
Store a fixed value into an input location. The
value is entered in scientific notation; the
absolute value of the number may range from 1
x 10
-19
to 9 x 10
18
. A value smaller than the
minimum is set to 0, while a larger value is set
to the maximum.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
FP
Mantissa
[F]
02:
2
n (Exponent of 10)
03:
4
Destination for input
location
[Z]
Input locations altered:
1
*** 31 Z = X ***
FUNCTION
Copy data from one input location to another.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
4
Source input location
number
[X]
02:
4
Destination input
location
[Z]
Input locations altered:
1
*** 32 Z = Z + 1 ***
FUNCTION
Add 1 to the current value in the specified input
location.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
4
Destination input
location
[Z]
Input locations altered:
1
*** 33 X + Y ***
FUNCTION
Add X to Y and place result in a third input location.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
4
Input location of X
[X]
02:
4
Input location of Y
[Y]
03:
4
Dest. input location of
X+Y
[Z]
Input locations altered:
1
*** 34 X + F ***
FUNCTION
Add F to X (where F is a fixed floating point
number) and place the result in an input location.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
4
Input location of X
[X]
02:
FP
Fixed value
[F]
03:
4
Dest. input location of
X+F
[Z]
Input locations altered:
1
*** 35 X - Y ***
FUNCTION
Subtract Y from X and place the result in an
input location.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
4
Input location of X
[X]
02:
4
Input location of Y
[Y]
03:
4
Dest. input location for
X-Y
[Z]
Input locations altered:
1