SECTION 13. CR23X MEASUREMENTS

13-22

FIGURE 13.5-2. Excitation and Measurement Sequence for 4 Wire Full Bridge

TABLE 13.5-1. Comparison of Bridge Measurement Instructions

Instr. Circuit

Description

4

DC Half Bridge User entered settling time allows compensation for capacitance in long lead

lengths. No polarity reversal. One single-ended measurement. Measured
voltage output.

5

AC Half Bridge Rapid reversal of excitation polarity for ion depolarization. One single-ended

measurement at each excitation polarity. Ratiometric output.

6

4 Wire

Slightly lower noise than 9. One differential measurement at each excitation

Full Bridge

polarity. Ratiometric output.

7

3 Wire

Compensates for lead wire resistance, assuming resistance is same in both

Half Bridge

wires. Two single-ended measurements at each excitation polarity. Ratiometric
output.

8

Differential

Makes a differential measurement without reversing excitation polarity or

Measurement switching inputs. Used for fast measurements on load cells, PRTs etc.
with Excitation Resolution and common mode rejection worse than 6 if used with delay=0.

Measured voltage output.

9

6 Wire

Compensates for lead wire resistance. Two differential measurements at each

Full Bridge

excitation polarity. Ratiometric output.

or 4 Wire
Half Bridge