SECTION 9. INPUT/OUTPUT INSTRUCTIONS

9-19

04:

4

# Cycles to measure

05:

4

Time out (0.01 sec, at
least the maximum
duration of the number
of cycles specified + 1
1/2 cycles.)

06:

4

Destination input
location

07:

FP

Multiplier

08:

FP

Offset

Input locations altered: 1 per repetition

*** 28 VIBRATING WIRE ***

MEASUREMENT

FUNCTION
Excites a vibrating wire sensor with a swept
frequency (from low frequency to high), then
measures the response period and calculates 1/T

2

,

where T is the period in ms. Excitation is normally
provided before each repetition. As an option, a
single excitation can be made prior to all repetitions
of the measurement. An AVW1 or AVW4 Vibrating
Wire Interface is usually required for these sensors.

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

2

Repetitions Hit C (--) to
skip repeat of
excitation

02:

2

Single-ended channel
for first measurement

03:

2

Excitation Channel

04:

2

Start frequency of
sweep (100'S of Hz)

05:

2

End frequency of
sweep (100'S of Hz)

06:

4

# Cycles to measure (0
means none)

07:

4

Delay before excitation
applied (0.01 sec units)

08:

4

Input location (1/T

2

), T

in ms

09:

FP

Multiplier

10:

FP

Offset

Input locations altered: 1 per repetition

*** 29 INW PS9105E ***

FUNCTION
The Instrumentation Northwest PS9105
Pressure Transducer is used to measure water
level. This instruction excites the PS9105 with

a single excitation channel and measures the
sensor’s output on two consecutive differential
analog input channels. The pressure and
sensor temperature are written into two
consecutive input locations starting at the
location specified in parameter 3.

Each PS9105 has 20 enhanced measurement
parameters that are documented on the
calibration sheet. Enter these parameters into
Instruction 29.

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

2

Differential channel
number for first
measurement

02:

2

Excitation channel
number

03:

4

Input location number

04:

FP

Pressure Range (psig)
(enh. par. 1)

05:

FP

Enhanced Parameter 2

06:

FP

Enhanced Parameter 3

07:

FP

Enhanced Parameter 4

08:

FP

Enhanced Parameter 5

09:

FP

Enhanced Parameter 6

10:

FP

Enhanced Parameter 7

11:

FP

Enhanced Parameter 8

12:

FP

Enhanced Parameter 9

13:

FP

Enhanced Parameter 10

14:

FP

Enhanced Parameter 11

15:

FP

Enhanced Parameter 12

16:

FP

Enhanced Parameter 13

17:

FP

Enhanced Parameter 14

18:

FP

Enhanced Parameter 15

19:

FP

Enhanced Parameter 16

20:

FP

Enhanced Parameter 17

21:

FP

Enhanced Parameter 18

22:

FP

Enhanced Parameter 19

23:

FP

Enhanced Parameter 20

Input location altered: 2

*** 100 SDM TDR ***

FUNCTION
Instruction 100 is used to control and measure
the CSI TDR Soil Moisture Measurement
System with control ports C1, C2, and C3. See
the TDR manual for information on Instruction
100.