Warnings and errors – Vaisala Hydromet Data Collection Platform User Manual
Page 133

Chapter 4 ___________________________________________________________ Troubleshooting
VAISALA______________________________________________________________________ 131
The measurement TAMeasQMH101_1 is defined in the setup file. The
command with the raw parameter produces the following response:
/ > LASTVAL TAMeasQMH101_1 unconv
Status:1 Value:109.508383
When the value in the report changes to ////, you can check the value. In
the following case, the probe is not connected:
/ > LASTVAL TAMeasQMH101_1 TA
Status:2 Value:-231.156481
When the value is invalid, check the sensor status value and refer to
:
/ > LASTVAL TAMeasQMH101_1 status
Status:1 Value:0
Warnings and Errors
There may be some problems if you see either of the following prompts:
/ E>
/ W>
/ E>
means that there are errors, and
/ W>
means that there are
warnings.
where
Status:1
=
Value is valid.
Value:109.508xxx =
Unconverted value [ohms] of PT100
measurement
where
Status:2
=
Value is invalid.
Value:-231.15xxxx =
Temperature measurement indicating that the
probe is not connected
where
Status:1
=
Status field in the output is the value status.
Value:0
=
Value field shows the sensor status.